LC-II Control Switch Kit
This
kit contains:
A microprocessor-based
motor controller that can be mounted in a standard electrical
box.
A gold-plated
Rain Sensor.
A white
face plate.
A
24VAC 50VA Free-Air
Transformer
with a mounting plate (shown in picture) or a
24VAC 50VA
Plug-In
Wall Transformer.
The LC-II Control Switch can operate up to three motors (three Standard
Motor Kits or Skylight
Motor Kits or one Standard
Motor Kit with up to two Motorized
Locks). When opened or closed, each window
moves in sequence to the same position. Independent
control of a single window in a group wired to a
common LC-II Control Switch is not possible.
The LC-II Control Switch can be controlled from an RS
Module and/or an IR Receiver.
The LC-II Control Switch can also be integrated
into a home automation system by connecting its remote switch
inputs to a properly configured thermostat,
X-10 ® Universal
Module, or other SPST (Single-Pole, Single-Throw) switch.
It also has a Rain Sensor which
will close windows automatically when rain is detected.
To see how an LC-II Control Switch integrates with all of our
other components to form a complete system for motorizing your
casement, awning, and skylight windows, take a look our wiring
diagram. It should give you a basic guideline for planning
and creating your own motorized window system.
|
| Price: $284.95 USD |
|
|
Part
No. LCIICSK01 |
- |
LC-II Control Switch Kit with Free-Air
Transformer. |
| Price: $247.95 USD |
|
|
Part
No. LCIICSK02 |
- |
LC-II Control Switch Kit with Plug-In
Wall Transformer. |
 |
|
|
LC-II Control Switch Installation Instructions
You can download
the Motor System Installation Instructions (1.26MB) to
familiarize yourself with the LC-II Control Switch installation.
The installation instructions are in Adobe PDF format and require
Adobe's free Acrobat Reader. If you don't have Acrobat Reader
you can download
it from Adobe's website.
Step 1 - Gather Your Tools
- #2 Philips head screwdriver
- 1/8" (3.0 mm) bladed screwdriver
- 1/10" (2.5 mm) bladed screwdriver
- Electric drill motor
- Drill bits (1/4" and 1/16")
- An awl for marking mounting holes
- Class II, low voltage wire for the motors, switches,
and transformers
- An assortment of wire nuts
Step 2 - Run Electrical Wires
- Use Class II stranded wire for all connections.
- Use the table below to select the wire size for transformer
and motor connections. Stranded wire is recommended
for all
transformer and motor connections.
- Run the wires to the motors, switches, and transformers.
Low voltage wires should be at least 12" away from
high voltage (120 VAC or higher) wires to avoid any electrical
interference.
| Class II Wire Size |
Total Distance Transformer
To Farthest Window |
| 18 AWG stranded |
50 ft (15 m) maximum |
| 14 AWG stranded |
100 ft. (30 m) maximum |
| 12 AWG stranded |
150 ft. (45 m) maximum |
Step 3 - Install Rain Sensor
- Do Not use the Rain
Sensor if the window or skylight is being used as
a smoke vent or if "Open & Hold" is required.
Refer to Open & Hold Switch Installation.
- Install the Rain Sensor
with the "grid" exposed. To avoid water pooling,
do not mount flat.
- The Rain Sensor can be mounted
outside (maximum sensitivity) or inside the vent edge
(minimum maintenance).
- A Rain Sensor can be connected
to every LC-II Control Switch, RS
Module, and IR Receiver
in your system. However, when RS
Modules or IR Receivers
are used the Rain Sensor
could be connected to one of them and not to the LC-II
Control Switch.
- Use 22 AWG, 2-conductor, shielded, twisted-pair wire,
50 ft. (15 m) maximum. Run low voltage wires at least
12" away from high voltage wires to avoid any electrical
interference. Connect the shield to GROUND (G). Refer
to the wiring diagram
for more information.
Step 4 - Install LC-II
Control Switch Jumper Setting
 
Jumper Block
1. Verify the jumper setting on the LC-II Control
Switch is correct for your application.
A - For windows with Motorized
Locks.
B - For skylights.
C - For windows without Motorized
Locks (no jumper installed).
|
Step 5 - Connect LC-II Control Switch
1.
The LC-II Control Switch can control up to three
matching sized windows, OR three
matching skylights, OR one window
with up to two Motorized
Locks.
2. Connect the LC-II Control Switch per the wiring
diagram and the LC-II Connectors table below.
There must be one transformer for each LC-II Control
Switch.
3. Mount the LC-II Control Switch in a single gang
electrical box. |
LC-II Connectors
Step 6 - Connect Transformer
1.
Install a Free-Air
Transformer (pictured to the
left) on a 4" x 4" junction box in a
cool, dry location. The surrounding air temperature
must not exceed 150° F (65° C). A Plug-In
Wall Transformer can be plugged into any convenient
wall socket.
2. Connect the transformer per the wiring
diagram. There must be one transformer for
each LC-II Control Switch.
Note: Installation must meet local and National
Electrical Codes (N.E.C).
Note: Connecting the transformer directly
to the motor can cause damage. |
Step 7 - Powering
Up the System and Testing
Note: Before powering up the system all motors must
be installed and correctly wired per Steps 1 through 6.
Because some windows open clockwise when the handcrank is
turned and some open counter-clockwise it is important to
determine which direction the skylight travels when power
is applied.
- Upon connecting power to the transformer wait 15 seconds
without pushing any buttons. The system should automatically
close all windows. Windows already closed should remain
closed.
- If any of the units open, power should be disconnected
and the motor wires to those units must be reversed
either at the motor or at the switch.
- If any of the units fail to open or close, see
the Troubleshooting Guide
below.
- If all windows closed correctly, press the "Reset"
button on the front of the LC-II Control Switch. After
a few seconds the LC-II Control Switch will automatically
open each window/skylight to its full range of available
travel. The LC-II Control Switch will then close each
window/skylight. This procedure may take several minutes.
Once the windows/skylights have closed again, the system
is ready for normal operation.
- After the system has been "Reset", momentarily
pressing "Open" will open all units, one at
a time, to the automatic vent position (approximately
80% of available travel). The units may be opened further
for cleaning or servicing by holding the "Open"
button after the vent position is reached. "Close"
will completely close all units from any position. Note:
Special open positions can be attained by pressing the
button for the opposite direction of travel while the
motor is running. This will halt the moving unit and move
all other units to the same approximate position.
- Each screen interlock must be checked when the unit
is running. The motor should stop when the screen interlock
is disconnected. Correct installation is the responsibility
of the installer. Note: The system must be reset after
each test.
Troubleshooting Guide
| Symptom |
Possible Solution |
| Unit does not operate, no sound from the motor. |
1. Press the "Reset" button on the LC-II
Control Switch to reinitialize the system.
2. Refer to the wiring
diagram and check the connections.
3. Check for power at the transformer for 110-125 VAC
input and 24 VAC output.
4. Check the screen interlock connection. |
Unit makes a noise, but the
window/skylight will not move
or operates erratically. |
1. Press the "Reset" button on the LC-II
Control Switch to reinitialize the system.
2. Be sure the window is unlocked.
3. Be sure the window will operate freely without the
motor attached.
4. Remove the motor cover and test. Be sure the cover
screw length is #6 x 3/8 PH.
5. LC-II Control Switch may be incorrectly
wired to the motor. Refer to the wiring
diagram.
|
| Unit runs slowly. |
1. Due to gear reduction in different operators, the
speed will vary. Skylights, due to very low gearing,
are normally slower. |
| Unit does not close completely. |
1. Press the "Reset" button on the LC-II
Control Switch to reinitialize the system.
2. Be sure the window will operate freely without the
motor attached.
3. Disconnect the power and refer to Step
7, Powering Up the System and Testing.
4. Check the jumper setting for the application. Refer
to Step 4, Install LC-II Control Switch
Jumper Setting. |
| Unit runs continuously in one direction when bench
testing. |
1. The motor must be connected to a window
for correct operation. Note: Connecting the
transformer directly to the motor can cause damage. |
| Unit closes when the "Open" button is pressed. |
1. Motor leads are reversed. See Step
7, Power Up the System and Testing. |
Optional Control Input Instructions
Control Input Priority
- Momentary contact closure will cause
the system to respond to the last command given.
- Continuous contact closure will override
any momentary contact closure.
- A continuous contact closure to open
has a higher priority than any contact closure to close.
- The Rain Sensor, since it
is not a contact closure, will close the unit(s) even
if the unit(s) is held open by a continuous contact open
command. When the Rain Sensor
dries off the unit(s) will again open.
Open & Hold Switch Installation
- This feature is designed for use with thermostat
and smoke vent systems. Note: DO NOT
use Open & Hold Switches with a Rain
Sensor because the Rain Sensor
will override the Open & Hold Switch.
- Use a SPST (Single-Pole, Single-Throw) continuous contact
relay or switch for this low voltage control application.
- Connect the controlling contact between the OPEN (O)
and GROUND (G) connectors on the LC-II Control Switch.
- When this contact is held closed the unit(s) will open,
and remain open, regardless of the state of any other
inputs, except for the Rain Sensor.
Close & Hold Switch Installation
- This feature can be used when leaving a building to close
the unit(s) and prevent any unattended device (such as
a thermostat)
from opening the unit(s). It can also be used for a security
system interface. This feature should not be
relied upon for security system purposes.
- Use a SPST (Single-Pole, Single-Throw) continuous contact
relay or switch for this low voltage control application.
- When an IR Receiver is NOT
used, connect the controlling contact between the CLOSE
(C) and GROUND (G) connectors on the LC-II Control Switch
and/or the RS Module. When
using an IR Receiver the
contacts should be between the CLOSE & HOLD (F) and
GROUND (G) connectors on the IR
Receiver.
- The "Close & Hold" feature overrides all
inputs except "Open & Hold".
|